Skip links
Distribution Products

Re-closers & Sectionalizers

VOLTAK Recloser / Sectionalizer: High-Efficiency Power Distribution Solutions

Conforming Standards and Specifications:

  • Meets international standards IEC62271-111 and IEEE C37.60.
  • Suitable for voltage ratings ranging from 6kV to 38kV.
  • Capable of handling a continuous current of up to 800A.
  • Short time current rating up to 16kA for 3 seconds.

Versatile Applications:

Designed for a broad range of applications, our reclosers and sectionalizers are ideal for:

  • Smart grid applications, including auto-changeover schemes.
  • Connection solutions for mobile switchgears, underground to overhead transitions, and generator integrations.
  • Use in mining equipment connections, substation circuit breakers, and renewable and distributed generation connections.

Innovative Design Features:

  • Utilizes solid dielectric and vacuum interruption for enhanced performance, free from oil and SF6.
  • Equipped with arc fault venting for safety.
  • Incorporates 3 integrated current transformers and 6 integrated voltage sensors for accurate monitoring.
  • Bidirectional operation with no active electronics, ensuring reliability.
  • Hermetically sealed with durable stainless steel construction.
  • Includes a steel mounting bracket for easy installation.
  • Features an IP66 stainless steel enclosure, operable in extreme temperatures ranging from -40°C to +55°C.
  • The connection between switchgear and controller uses a fully armored cable.
  • Integrated GPS in RC15 model for precise event timestamping without the need for external communications.

Key Technical Parameters:

  • Current Sensing: Enabled by 3 current transformers.
  • Voltage Sensing: Managed by 6 voltage screens.
  • Fault Make Capacity: Ranging from 12.5kA to 16kA RMS, with a peak capacity of 31.5kA to 40kA.
  • Rated Continuous Current: Consistently manages 800A.
  • Mechanical / Full Load Operations: Up to 30,000 cycles.
  • Fault Break Capacity: Efficiently handles 12.5kA to 16kA.
  • Short Time Current Withstand: Robust design withstands up to 16kA for 3 seconds.